您好,欢迎来到爱go旅游网。
搜索
您的当前位置:首页低压开关柜招标技术规格书

低压开关柜招标技术规格书

来源:爱go旅游网


低压开关柜技术规格书

二零一七年四月

目 录

1 总则 ······················································································································ 1 2 工程概况 ··············································································································· 2 3 标准和规范 ··········································································································· 3 4 供货范围 ··············································································································· 4 5 技术数据 ············································································································· 10 6 结构、设计与性能 ······························································································· 14 7 试验 ···················································································································· 23 8 工厂检验与监造 ·································································································· 24 9 设计联络会 ········································································································· 25 10 现场技术指导和培训服务 ····················································································· 26 11 质量保证 ············································································································· 27 12 技术资料 ············································································································· 28 13 包装与运输 ········································································································· 30 14 附图 ···················································································································· 31

1

1.1

总则

本技术规格书适用于一期工程400V低压开关柜、电动机控制中心(MCC)低压

开关柜、照明配电箱、插座箱、就地控制箱、就地控制按钮盒、低压封闭母线槽、与厂变连接裸母线及附属设备等。技术规格书提出了开关柜及其附属设备的功能、设计、结构、性能和试验等方面的技术要求。 1.2

卖方提供的设备应是符合本技术规格书、适用于交流额定电压400V,额定频率

50Hz的火力发电厂厂用电系统的完整的成套开关设备。 1.3

买方在本技术规格书中提出了最低限度的技术要求,并未规定所有的技术要求

和适用的标准,卖方应提供一套满足本规范和所列标准要求的高质量产品及其相应服务。对国家有关安全、环境保护等强制性标准,必须满足其要求。 1.4

设备采用的专利涉及到的全部费用均被认为已包含在设备报价中,卖方应保证

买方不承担有关设备专利的一切责任。 1.5

卖方应按照本技术文件的要求,负责其供货范围内全部设备的设计、制造、设

备配套、油漆、包装,指导设备安装、调试和试验,并对最终用户进行培训。卖方所提供的产品应是技术和工艺成熟先进,并经过多年连续运行实践已证明是成熟、安全、可靠的优质产品。 1.6

卖方在设备设计和制造中所涉及的各项规程、规范和标准必须遵循现行最新版

本的中国标准和IEC标准。本技术规格书所使用的标准如遇与卖方所执行的标准发生矛盾时,应按较高标准执行。 1.7

在签订合同之后,如果因国家或行业相关规范、标准和规程发生变化,或者项

目技术方案发生变动,买方有权提出对本技术规格书进行补充、修改等变更要求,只要技术上可行,卖方都应予以答应和接受。若因技术规格书的变更导致商务价格的变化,将由买、卖双方根据商务合同相关规定共同商定变更后的价格。 1.8

设备的外购件,卖方应按买方指定的厂家、品牌选择,对于买方没有指定的,

卖方应选用知名厂家的产品,并提交买方确认。买方对任何产品的指定或确认,并不代表买方将对这些产品承担责任,也不能减轻卖方对所供设备应当承担的责任。卖方应对整套设备包括其所有部件、元件、材料的性能、质量负全责。 1.9

卖方提供的设备,应是组装成套的完整设备,设备上安装的,以及按本技术规

格书要求单独提供的所有部件、元件和材料,均应视为设备的构成。

1.10 除非另有说明,卖方提供的设备的设计使用寿命应达到30年。

1.11 本技术规格书经卖方、买方确认后作为订货合同的技术附件,与合同正文具有同等的法律效力。若商务合同与本文件有矛盾之处,对于供货范围、技术要求等技术事项的内容,应以本技术文件为准,而对于商务方面的内容,则应以商务合同为准。

2

2.1

工程概况

概述

本项目一期规模为600t/d,二期新建相同焚烧线规模;本项目总占地面积为206亩。 2.2

工程条件

本技术文件要采购的设备,其安装地点的环境和系统条件见表1。卖方应对所供设备的绝缘水平、温升等相关性能参数在以下工程条件下进行校验、核对,使之满足相应工程条件和设计工况的要求。低压系统绝缘配合及海拔修正的详细规定见GB/T 16935标准。

曹县属温带性季风型半湿润气候区,其特点是气候温和,光照充足,热量丰富,雨量适中,四季分明,温差大,雨热同季,光、热、水、气匹配比较好,但年际间降水量变化较大,灾害性天气较频繁。

年日照时数 无霜期 极端最高气温 极端最低气温 最大年降水量 多年平均降水量 日最大年降水量 连续7日最大降水量 最大冻土浓度 最大积雪浓度 全年主导风向 冬季平均室外风速 夏季平均室外风速

20小时 212天 43.3℃ -17.9℃ 1223.3mm 686.4mm 236mm 2009mm 290mm 200mm 东南风 2.8m/s 2.4m/s

最冷月平均相对温度 最热月平均相对温度 全年平均相对温度

67% 78% 69%

3

3.1

标准和规范

卖方提供的所有设备和部件(包括卖方方向其他厂商购买的所有附件和设备)

都应遵守最新的国家标准(GB)和国际电工委员会(IEC)标准以及国际单位制(SI)标准。 3.2

所有螺栓、双头螺栓、螺纹、管螺纹、螺栓夹及螺母均应遵守国际标准化组织

(ISO)和国际单位制(SI)的标准。 3.3

设备和部件应符合以下标准但不局限于以下标准: (1) GB7251 低压成套开关柜

(2) IEC– 439 低压成套开关设备及控制设备 (3) ZBK36001 低压抽出式成套开关设备

(4) GB/T14048.1 低压成套开关设备及控制设备 总则 (5) GB/T14048.4 低压成套开关设备及控制设备

低压机电式接触器和电动机 起动器

(6) GB/T14048.5 低压成套开关设备及控制设备 控制电路电器和开

关元件 第一部分 分机电式控制电路电气

(7) GB191 包装储运图示标志

(8) JB794 电机、电器和变压器用绝缘测量耐热分级 (9) IEC-470 交流接触器 (10) GB4208 外壳防护等级的分类

(11) DL/T5153 火力发电厂厂用电设计技术规定 (12) DL/T5222 导体和电器选择设计技术规定 (13) SDJ9 电气测量仪表装置设计技术规定

(14) GB 50171 电气装置安装工程盘、柜及二次回路接线施工及验 收规范

(15) GB 2887 电子计算机场地通用规范

(16) GB/T 7267 电力系统二次回路控制、保护屏及柜基本尺寸系列

(17) GB/T 7450 电子设备雷击保护导则

(18) GB/T 14537 量度继电器和保护装置的冲击和碰撞试验 (19) JB/T 9568 电力系统继电器、保护及自动装置通用技术条件 (20) GB/T 587 微机继电保护装置运行管理规程 (21) DL/T 621 交流电气装置的接地

(22) DL/T 659 火力发电厂分散控制系统在线验收测试规程 (23) DL/T 478 静态继电保护及安全自动装置通用技术条件 (24) DL/T 5136 火力发电厂、变电所二次接线设计技术规定 (25) DL/T 5137 电测量及电能计量装置设计技术规程 (26) DL/T 5147 电力系统安全自动装置设计技术规定 (27) GB 4943 信息技术设备(包括电气事务设备)的安全 (28) GB/T 16935 低压系统内设备的绝缘配合 (29) 元件生产国的国家标准 (30) 其它有关标准 3.4

如果卖方选用本规范书上规定以外的标准时,则需提交这种替换标准供审查和

分析,仅在买方已证明替换标准相当或优于规范书规定的标准,并从买方处获得书面认可后才能使用。提供审查的标准应为中文版本。 3.5

以上标准和规范均执行已经颁布的最新版本。

4 供货范围

卖方的供货范围包括以下的设备和部件,每项都应包含在总价中。卖方在商务报

价书里应按以下表格的内容逐一列出分项价格。 4.1

成套设备

卖方应提供表2所列的成套设备。

表2 供货范围——成套设备清单

序号 1 货物名称 型号规格 29面 数量 备 注 详细配置见附图,包括与厂用干变的连接母排 #1~#2厂用PC段低压MNS, 400V, 5000A 抽出式开关柜

序号 2 货物名称 型号规格 2面 数量 备 注 详细配置见附图,包括与厂用干变的连接母排 详细配置见附图,包括与厂用干变的连接母排 详细配置见附图 低压备用段低压抽出MNS, 400V, 5000A 式开关柜 低压保安段低压抽出MNS, 400V, 5000A 式开关柜 #1焚烧MCC低压抽MNS, 400V, 1600A 出式开关柜 #1汽机MCC低压抽MNS, 400V, 1600A 出式开关柜 主控楼MCC低压抽MNS, 400V, 1600A 出式开关柜 综合泵房MCC低压MNS, 400V, 1600A 抽出式开关柜 油泵房MCC低压固GGD, 400V, 1600A 定式开关柜 综合泵房消防MCCGGD, 400V, 1600A 低压固定式开关柜 主厂房消防MCC低MNS, 400V, 1600A 压抽出式开关柜 机修间配电柜 MNS, 400V, 1600A 3 5面 4 6面 5 4面 详细配置见附图 6 4面 详细配置见附图 7 4面 详细配置见附图 8 2面 详细配置见附图 9 4面 详细配置见附图 10 2面 详细配置见附图 11 1面 详细配置见附图 12 PC段母线桥 13 照明、风机配电箱 14 控制按钮盒 报综合单价,不连接汽机、锅炉PC段400V, 4000A 计入总价。数量与备用段 以实际为准 宿舍楼、主控楼照明箱采用暗装,其他厂房均NXM、FJDM、JXF138(数量以图纸采用明装。若无特殊说等 为准) 明,照明箱厚度不大于120mm,照明箱安装高度底边距地1.3m。 LA101K-1BS(配LA101P-JZ 220V60 事故风机 交流) 触点两常开两

序号 货物名称 常闭 型号规格 数量 备 注 15 16 17 18 19 20 21 22 23 24 25 26 就地按钮盒 铁壳开关 铁壳开关 铁壳开关 铁壳开关 检修电源箱 电磁启动器 电磁启动器 电磁启动器 电磁启动器 电磁启动器 电磁启动器 仪控盘柜清单: FJD3-AAP(300x180x40 160) HH12 100/3 HH12 80/3 HH12 60/3 HH12 30/3 JXX-1系列 MSB-0.16A 380V MSB-0.29A 380V MSB-0.52A 380V MSB-1.3A 380V MSB-1.8A 380V MSB-6A 380V 14 2 2 2 20 2 2 4 4 2 2 急停按钮 序号 设备名称 型 号 外形尺寸 电源柜 单位 数量 备 注 原理图

序号 1 2 设备名称 型 号 外形尺寸 单位 面 面 数量 1 1 备 注 防护等级:IP45 防护等级:IP45 防护等级:IP55 防护等级:IP55 防护等级:原理图 AM2 AM1 仪控220V交流电源柜 UPS及直流电源柜 800x2200x600(mm)宽x高x深 800x2200x600(mm)宽x高x深 热力配电箱 800x2200x600(mm)宽x高x深 800x2200x600(mm)宽x高x深 800x2200x600(mm)宽x高x深 800x2200x600(mm)宽x高x深 壁挂式配电箱 04H14S-06Y04 04H14S-03Y04 3 4 AP1 AP61 1#锅炉热力配电箱 1#汽机热力配电箱 汽机公共热力配电箱 综合水泵房热力配电箱 面 面 1 1 04H14S-03Y04 04H14S-06Y04 5 AP71 面 1 IP55 防护等级:04H14S-06Y04 6 AP81 面 1 IP55 04H14S-08Y02 7 11CSB21-26 壁挂式配电箱 8 11CSB27 壁挂式配电箱 550X380X130(mm)宽x高x深 6分支回路 550X380X130(mm)宽x高x深 6分支回路 接线盒 防护等级:面 6 IP55 (防爆等级:面 1 Exd ⅡA T3) 04H14S-03Y04 04H14S-03Y04 9 端子数:32 进线孔:12个DN20 出线孔: 10HJY01 防爆接线盒 2个DN40 面 0.5~2.5mm2 下进上出 注:以上电源柜及热力配电柜均为GGD型; 1 (防爆等级:Exd ⅡA T3) 说明: 1) 以上设备应按附件单线配置图组柜成段,供货范围包含每段的母线及紧固件等。

2) 以上设备为成套的完整设备,包括设备上的所有部件、装置、元器件、仪表、内部连接线等。尽管有的部件、装置、元器件、仪表在本技术文件里没有列出或者明确要求,但根据相关技术规范要求或者根据今后的详细设计要求,它们是开关柜需要配置的,卖方也应按要求在开关柜上提供,并且这部分的价格已经包括于设备总价中,卖方不得因此增加价格。

3) 供货范围和配置明细应以本技术规格书及附图为准,若商务文件中分项价格表中列出的设备、元件清单中存在漏项或者数量不足,所有缺漏项和数量不足项都应视为已经包含在设备总价中,卖方应按本技术规格书的要求完整供货,合同价格不得增加。 4.2

备品备件

卖方应提供必要的随机备品备件,数量满足安装、调试和18个月质保运行的需要,规定的随机备品备件数量要求见表3,随机备品备件的价格应包含在合同总价中。

随机备品备件的详细清单及其分项价格在商务文件中列出,若按本技术规格书表3的要求,商务文件中所列的随机备品备件清单存在漏项或者数量不足,所有缺漏项和数量不足项都应视为已经包含在设备总价中,卖方应按本技术规格书的要求完整供货,合同价格不得增加。

推荐备品备件清单及对应的价格在商务文件中列出,在合同执行期间(包括质保期),买方可按该清单及报价向卖方进行选择性订购。推荐备品备件不在本合同供货范围之内。

所有备品备件应是新品,与设备同型号、同工艺。

如因为产品质量问题,或者由于卖方其它过错造成安装、调试和质保运行期间零部件损坏或缺损,将先用已有的备品备件用来更换,之后卖方应及时免费发货补齐。

表3 供货范围——随机备品备件

序号 1 2 3 4 5 6 7 名称 框架断路器跳闸线圈 框架断路器合闸线圈 规格型号 CW3系列 CW3系列 数量 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 备注 框架断路器智能保护脱CW3系列 扣器 塑壳断路器 电机智能保护器 接触器 热继电器 CM3系列 UNT-MMI-B系列 CK3系列 CJR3系列

序号 8 9 指示灯 继电器 名称 规格型号 AD11 MY4NJ 6L2-A 6L2-V JD194-BS4I PZ96 MNS柜配件 MNS柜配件 RT28N-32 CH1系列 MNS柜配件250A MNS柜配件16线,24线 数量 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 每种规格各*只 备注 10 电流表 11 电压表 12 变送器 13 多功能表 14 抽屉把手 15 抽屉开关操作手柄 16 熔断器 17 辅助回路空气开关 18 抽屉柜一次触头 19 抽屉柜二次触头 20 其它易损部件 见商务文件详细备件清单 4.3 专用工具

卖方应至少提供表4所列的专用工具及仪器,满足设备安装、运行、检修需要。

(卖方应根据自身设备特点进行必要的增补)

表4 专用工具清单

序号 1 2 3 名 称 框架断路器、隔离开关推进机构操作工具 框架断路器、抽屉检修转运小车 安装扳手套装 型号及规范 摇把 各种需要的规格 数量 2 2 1 备注 安装扳手套装

4 柜门钥匙 MNS柜和GGD柜 20 5 技术数据

卖方所供主要设备和部件应满足表5技术数据表的要求。

表5 主要设备和部件技术数据表

序号 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 项目 开关柜一般规定 型式 额定工作电压 额定绝缘电压 额定频率 1min工频耐压 母线配置 母线材质 主母线规格 分支母线规格 PC段 单位 V V Hz kV A A 要求 低压抽出式:MNS型 低压固定式:GGD型 400 690 50 8 见附图 铜 不低于附图规定 不低于附图规定 5000(相母线) 2500(中性线) 1600(相母线) 800(中性线、地线) 1250A(相母线) 800A(中性线、地线) 1250 1000A 主母线额1.10 定电流 锅炉、汽机、宿舍楼、综合水泵房MCC 主厂房消防设备配电柜、消防水泵配电柜 PC段 A A A 1.11 锅炉、汽机、综合楼、分支母线综合水泵房MCC (垂直母线)额定电主厂房消防设备配电流 柜、消防水泵配电柜 A 1000A 100(主母线) 50(分支母线) 50 主母线和分支母线锅炉、汽机、综合楼、额定短时1.12 综合水泵房MCC 耐受电流(3s,有效主厂房消防设备配电值) 柜、消防水泵配电柜 PC段 kA kA kA 50

序号 项目 PC段 单位 kA kA 220(主母线) 110(分支母线) 110 要求 主母线和分支母线1.13 额定峰值耐受电流 锅炉、汽机、综合楼、综合水泵房MCC 主厂房消防设备配电柜、消防水泵配电柜 高 kA mm mm mm V V kV Hz A kA kA V V V kV Hz A kA kA 110 2200 1000、800、600(详见附图) 1000、600(详见附图 经硬铜排与紧挨的干变连接 下方电缆进出线 不低于IP 4X 常熟CW系列 400、690,3极 1000 12 50 400~5000 (详见附图) 70 65 DC220 常熟CM3系列 ABB Tmax系列 施耐德 NSX系列 400,3极 1000 8 50 10~630 (详见附图) 50 AC400V 50 AC400V 1.14 柜体尺寸 宽 深 1.15 进出线方式 PC段进线 其它进出线 1.16 防护等级 2 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 4 框架断路器 型号系列 额定电压 额定绝缘电压 额定冲击耐受电压 额定频率 额定电流 极限开断电流(有效值) 额定短时耐受电流(有效值,1s) 额定控制电压 塑壳断路器 型号系列 额定电压 额定绝缘电压 额定冲击耐受电压 额定频率 额定电流 额定极限短路分断电流(有效值) 额定运行短路分断电流(有效值) 电流互感器

序号 4.1 4.2 4.3 4.4 4.5 4.6 4.7 5 5.1 5.2 5.3 5.4 5.5 5.6 6 6.1 6.2 6.3 6.4 7 7.1 7.2 7.3 型号 额定电压 额定一次电流 额定二次电流 准确级 额定二次容量 制造厂 电压互感器 型号 额定一次电压 额定二次电压 准确级 额定二次容量 制造厂 交流接触器 型号系列 额定电压 线圈电压 额定电流 电动机保护器 型号 基本功能 制造厂 项目 单位 V A A VA V V VA V V A BH系列 380 详见附图 5 要求 PC段进线:10P15/0.5 其它回路:0.5s 10 大连北方 JDG系列 380/√3 100/√3 0.5 15 大连北方 常熟、施耐德相应产品 AC400,三极 AC220 详见附图 UNT-MMI-B 短路、堵转、过负荷、缺相、接地故障保护; DC 4~20mA模拟量输出 优耐特

序号 9 9.1 9.2 9.3 9.4 10 测量表计 型号 基本功能 工作电压 制造厂 项目 单位 V V V kV A kA 次 次 V TK-JDX 400V PZ96-E3 电量就地显示; 要求 DC 4~20mA模拟量输出 AC220 安科瑞 CAP2-**A/D/3 400 750 8 见附图 7.65(1S, 额定电流32A~100A); 17(1S, 额定电流125A~800A) 5000 1000 PC级 主厂房消防设备配电柜、消防水泵配电柜:自动; 其它开关柜:手动 双电源进线转换开关 10.1 型号 10.2 额定工作电压 10.3 额定绝缘电压 10.4 额定冲击耐受电压 10.5 额定电流 10.6 额定短时耐受电流 10.7 机械寿命 10.8 电气寿命 10.9 等级 10.10 操作型式 10.11 制造厂 11 11.1 11.2 11.3 11.4 12 数字智能消防巡检装置 型号 额定工作电压 防护等级 制造厂 备自投装置 常熟 WZX-110/4 400 IP42 保定泰华 PCS-9691C 5A,100V,DC220V PC段共2台。 南京南瑞 12.1 型号 12.2 装置工作电压 12.3 安装数量 12.4 制造厂 13 就地控制箱 13.1 型号 13.2 装置工作电压

序号 13.3 额定频率 13.4 防护等级 14 照明配电箱 14.1 型号 14.2 装置工作电压 14.3 额定频率 14.4 防护等级 15 项目 单位 TK-JXX 400V 50Hz IP TK-ANH 400V 50Hz IP65 PZ30 400V 50Hz IP33 50Hz IP 要求 就地控制按钮盒 15.1 型号 15.2 装置工作电压 15.3 额定频率 15.4 防护等级 16 铁壳开关 16.1 型号 16.2 装置工作电压 16.3 额定频率 16.4 防护等级 17 检修电源箱 上海人民(上联) HH12 400V 50Hz IP 17.1 型号 17.2 装置工作电压 17.3 额定频率 17.4 防护等级 18 电磁启动器 18.1 型号 18.2 装置工作电压 18.3 额定频率 18.4 防护等级 上海人民(上联) MSB 400V 50Hz IP43 6

6.1

结构、设计与性能

基本要求

本技术规格书中除按低压固定式开关柜设计外,其它低压开关柜均按低压抽出式

成套开关柜进行设计。宿舍楼配电柜具体配置及参数详见施工图。 6.2

柜架和外壳

(1) 设备的柜架为垂直地面安装的自撑式结构。

(2) 柜体的结构应允许电缆从柜体底部或顶部进入柜体。

(3) 开关柜的框架和外壳应是金属的,其外壳应采用优质敷铝锌钢板(δ≥2.0mm)制成。柜架和外壳应有足够的强度和刚度,应能承受所安装元件及短路时所产生的动、热稳定。同时不因成套设备的吊装、运输等情况而影响设备的性能。内部分隔板也选用进口覆铝锌板。并用无裂缝的钢板全部包成固定结构。对电流大于3200A的开关柜,卖方应采取措施以抑制涡流的产生。

(4) 开关柜内的设备布置应合理符合性能要求,框架内应留有足够的空间以便于检修,开关柜的上部结构、侧面结构、母线、控制接线应便于将来扩建和延伸。

(5) 为便于开关柜在运输和安装过程中搬运,开关柜应设计并提供可移动的起吊搬运手段。

(6) 开关柜装绞链门。在每个垂直部分的背面,装可拆卸的板或绞链门。 (7) 开关柜的外形应平整美观,内、外表层颜色由业主确定。 (8) 每台开关柜应内设温湿度控制器和驱潮加热器。 6.3

通风孔

(1) 通风孔的设计和安装应使得当熔断器、断路器在正常工作时或在短路情况下没有电弧或可熔金属喷出。

(2) 通风孔的尺寸、形状及安装位置不应使整个外壳的强度下降。

(3) 通风孔的位置不应降低外壳的防护等级,并能防止由上面滴水或地板上溅起的水进入开关柜内。

(4) 外壳顶部的通风孔应用覆板遮盖。 6.4

隔离

(1) 利用隔板可将开关柜划分成几个隔室,如母线隔室、电缆隔室、功能单元隔室等,以满足下述一种或几种要求:

- 防止触及邻近功能单元的带电部件; - 事故电弧的扩大;

- 防止外界物体从一个隔室进入另一个隔室。

(2) 隔室之间的开孔应确保熔断器、断路器在短路分断时产生的气体不影响相邻隔室的功能单元的正常工作。

(3) 用作隔离的隔板可以是金属板或绝缘板,金属隔板应与保护接地导体可靠连接,金属隔板在人体碰撞时的变形不应减小其绝缘距离,绝缘隔板则不应碎裂。

(4) 功能单元隔室中的隔板不应因为短路分断时所产生的电弧或游离气体所产生的压力而造成损害或永久变形。

(5) 装于柜体上的继电器,应能防止断路器或其它电气设备正常操作振动而误动作。 6.5

功能单元

(1) 即使主电路带电(但主开关应分断),也能用手直接或借助工具安全地将功能单元抽出或插入。

(2) 功能单元在单元隔室中应有三个明显的位置: - 连接位置; - 试验位置; - 分离位置。

(3) 当功能单元处于连接位置时,主开关处于分断位置时亦可视为试验位置。 (4) 位置指示可以采用位置指示标牌,也可借助操作机构的位置加以区别。 (5) 功能单元在6.5 (2)条中的三个位置都应有机械定位装置,不允许因外力的作用而从一个位置移动到另一个位置。

(6) 功能单元的主电路隔离接插件(包括进线和出线)应该跟随功能单元自动地接通和分离、辅助电路隔离接插件则可以是自动接通和分离,也可以通过手动来完成。

(7) 如功能单元上装有电路连接插头,它的动作状态是:

- 当主电路隔离接插件与主带电导体连接之前保护电路连接插头与外壳的

保护导体先接通。

- 当主电路隔离接插件与主带电导体分离后,保护电路连接插头才允许与

保护导体分离。

(8) 功能单元在连接位置的定位机构应保证当短路事故发生时不因电动应力而使主电路隔离接插件与主带电导体误接通。

(9) 相同的功能单元应具有互换性,即使是在短路事故发生后,其互换性也不能破坏。 6.6

联锁

应提供如下辅助开关和机械联锁:

(1) 安装一只位置开关,当断路器从“接通”位置抽出时应动作。该位置开关在断路器回复到“接通”位置之前,它应保持在动作的位置上。位置开关是用来使断路器从“接通”位置抽出时将断路器从“远方”变换到“就地”控制的。

(2) 功能单元与小室的门必须设置机械联锁。当主开关(断路器或熔断器式刀开关)处于分断位置,门才能打开,否则门打不开。

(3) 为了防止未经允许的操作,主开关的操作机构应能使用挂锁将其锁在分断位置上 。

(4) 当特殊需要时,可设置一个解锁机构,以便主开关处于接通位置时,也能将门打开。 6.7

主母线和分支母线

(1) 主母线、分支母线(包括抽屉的一、二次触头),选用高导电率的铜(>99.9%)材料制造并且镀锡。母线都应予以绝缘。开关柜母线(A、B、C、N)应加装热缩型绝缘护套。

(2) 母线采用螺栓连接时,每个连接头应不少于两个螺栓。 (3) 绝缘导线应选用铜制多股绞线。

(4) 主母线支架及母线绝缘材料应具有低吸潮特性,在设备使用寿命期间内设备的机械和介质强度不应降低。

(5) 应设置垂直母线关闭遮板,当可抽出单元抽出时可以防止意外触及垂直母线。

(6) 中性母线应全绝缘,其电流额定值应为相母线的50%及以上。该中性母线应由2根引线接到开关柜接地母线上,引线规格不低于接地母线规格。 6.8

二次回路元器件和接线

(1) 卖方所供设备应按要求配置必要的二次元器件,包括但不限于:继电器、电动机保护器、备自投装置、指示灯、按钮、转换开关、测量表计、二次端子等。附图中并没有列出所有二次元器件,对于没有列出的二次元器件,只要是为了满足本技术规格书、相关标准和规范、最终详细设计的要求所必需的,卖方都应提供,且不得因此增加合同价格。所有二次元器件都应在出厂前完成安装及接线。

(2) 继电器、智能电动机保护器不能布置在当柜门关闭或打开及抽屉抽出或推进

时将引起误动(引起合闸或跳闸)的地方。

(3) 所有元器件外接引线均应经端子排接入或引出。所有端子额定电压不低于500V,容量应满足回路要求,均为螺栓型,带有弹簧压板、隔板和标志排。开关柜金属分隔间隔及抽屉单元内的每组端子排应留有不少于总数的20%的备用端子。每个端子排对内及对外原则上只接一芯导线(电缆)。每个端子排将标有编号。

(4) 对于CT交流电流端子熔断器或空开前后端端子应设计成可短接型的,以便当校验或检修继电器或仪表时保护CT。

(5) 不需外部连接的电流和电压互感器的二次回路在电源侧应接地。需要接地的每一回路将单独地连接到设备接地母线上。

(6) 控制导线采用铜导线,截面不小于1.5mm2,用于电流互感器、电压互感器的单线截面不小于2.5mm2。单线为单芯、聚氯乙烯绝缘(阻燃型),额定电压不低于450/750V。交、直流回路的导线不应同束捆扎,弱电或通信回路应采用屏蔽导线连接。

(7) 每一个断路器、接触器的合闸、跳闸(控制)回路除交流操作的中性线外,均应设置熔断器或断路器作保护,柜内交流操作的中性线应从本柜中性线母线上取出,规范详见订货图。

(8) 如果某些布线的突然短路会引起设备误动,如引起开关的误合闸或误跳闸,则这些布线就不能连接在相邻的端子上。

(9) 导线的两端有擦不掉的、符合布线图的命名的永久性的标志。导线任何的连接部分不能焊接。

(10) 对于电源回路断路器应提供抽屉“工作位置”和“试验位置”限位开关常开接点至少3付,供买方使用。

(11) 二次元器件、保护压板、盘面上的元件均应采用有机玻璃的标志牌,标志牌刻有机组号及元件名称,标志牌布置在元件的下方。

(12) 断路器和接触器应有可靠的“防跳”接线。

(13) 为保证互换性,抽屉式开关柜同类设备(断路器、接触器等)的抽屉单元二次接线和二次插头应具有相同的接线和排列。

(14) 开关柜进线、大功率电动机回路、重要电动机回路和其它重要馈线需配置三相电流测量表计,每段低压开关柜的PT回路应配置三相电压测量表计。所有测量表计采用数字式产品,并能提供4~20mA远传模拟量信号(若测量表计不能提供,

则需另外单独配置相应的变送器)。

(15) 工艺电动机配智能电动机保护器。电动机保护器应具有电动机短路、过负荷、缺相、堵转、接地故障等保护功能,并配备4~20mA模拟量(电流)输出信号。

(16) PC段开关柜应配置电源备自投装置,装置应是微机型,详细技术要求见6.11章节。 6.9

保护接地

(1) 装置应设置能贯穿装置全长的接地母线。

(2) 装置的保护接地回路可由单独的保护接地母线和可导电的结构件构成。它应能保证装置的各裸露导电部件之间以及它们与保护接地回路之间的可靠连接。

(3) 所有作为隔离带电导体的金属隔板均应有效接地。

(4) 装置的框架、电气设备的金属外壳以及金属手动操作结构应有效接地。如果上述部件采用金属螺接安装在已经接地的镀锡、镀锌金属构件上,则认为已经充分接地。

(5) 保护接地母线应能承受装置在运输、安装时所受的机械应力和在单相接地短路事故中所产生的机械应力和热应力,其接地连续性不能破坏。 6.10 双电源进线自动转换开关

(1) 双电源转换开关要求采用PC级产品。

(2) 两路电源在的、绝缘封闭的空间内接通、分断、灭弧,以确保安全性。 (3) 两路电源采用的灭弧通道,在灭弧通道内设置多片金属灭弧栅,对产生的电弧进行分割、冷却,保证产品对外零飞弧,确保操作、维护人员的安全。

(4) 具有较高的短路接通及短路耐受能力,确保供电的连续性。 (5) 具有机械互锁功能,两路电源互为备用。 (6) 可带负荷分断和接通线路。

(7) 隔离功能:采用有明显隔离指示开关,以保证使用安全。 (8) 外壳材质:为减小环境对开关工作影响,采用阻燃环保材料。 (9) 可靠的接触指示。

(10) 执行标准:IEC60947-3/IEC60669-1/BS19/VDE0660/GB14048.3。 (11) 详细参数见表5和附图。 6.11 备自投装置

PC段微机型备用电源自动投入装置(共2套)

微机型400V工作段备用电源自动投入装置,安装于400V开关柜内。要求备自

投装置内含三个以太网络芯片,允许电接口或光接口通过以太网进行通信,同时支持双串口通信(RS485/MODBUS协议)。要求备自投装置带有直流B码对时接口。 本工程两台低压工作变压器采用明备用方式,设有专用备用变压器。 要求该装置应满足以下要求:

正常运行方式下应保证在一台工作电源断路器断开后,才能投入备用电源; 低压母线电压不论任何原因消失时,自动投入装置均应动作; 自动投入装置只允许动作一次;

应能通过设置控制字、外接压板或通信等方式进行一些基本的设置,例如:投入或退出备自投功能、设置装置的备自投方式等。

任一备用电源进线断路器闭合,应闭锁其他各段的备自投装置; 备自投方式的动作要求:

在工作段上备用电源进线断路器断开的运行方式下,当任一段400V工作母线失压时,若备用变400V侧母线有压,则跳开400V工作母线的进线断路器及对应的厂变高压侧开关,再合上失压的400V工作母线的备用400V断路器。

应提供装置启动指令,动作、装置故障或装置失电等信号接点,以便系统对其进行监控。

应具有控制字控制功能,控制字可分为自动、手动、解锁。设备具有人机对话功能时,对话界面应汉化,图标标准应便于识别和操作。 6.12 母线桥

(1) 母线桥导体的材质、截面应与开关柜导体一致,除三相工作母线外另需设置专用的中性工作母线,其两端应延伸至开关柜柜内以便分别与开关柜内的母线连接,低压封闭母线槽外壳为铝合金,与开关柜的连接应采用法兰。

(2) 开关柜和母线桥应在制造厂车间内拼盘,以保证现场开关柜和母线桥的可靠连接和柜面的平整;开关柜柜面的垂直度和水平偏差不大于1mm/1000mm。

(3) 卖方应提供安装母线桥所需的吊架。 6.13 开关柜与干式变压器柜的连接

(1) 低压开关柜与干式变压器均布置于配电室内、成一列布置,变压器由买方另购。

(2) 开关柜的母线应伸入变压器柜内,开关柜母线与变压器低压端子的连接由开关柜厂负责,铜母线由开关柜厂家提供,母线截面应满足变压器最大输出容量的要求。

(3) 安装和固定引出线端子板及母线的支柱或绝缘子的部件应有足够的强度,防止短路产生电动力使其破坏或发生位移。

(4) 变压器低压侧母线应全部布置于变压器罩壳内。卖方应与干式变压器厂家就低压开关柜母线的布置及接口尺寸、引出线端子板、连接板及母线的支柱绝缘子或绝缘子的安装问题进行配合,以便于设计变压器罩壳内低压母线的支持结构。卖方应保证变压器低压侧母线与开关柜母线连接接口的准确,以便在现场不需调整便可进行可靠连接。变压器柜内的支持结构所需材料和绝缘子由变压器厂提供。

(5) 低压母线穿出开关柜及穿入变压器柜处应设置保护套管,开关柜内保护套管由开关柜厂供货,卖方应就保护套管的尺寸、外形、安装位置与变压器厂配合。

(6) 开关柜的工作母线、中性母线、接地保护母线需与变压器柜内的低压出线端子、中性母线、接地保护母线对应连接。

(7) 卖方应与干式变压器供货商就变压器安装、各个母线的连接等问题进行配合,负责指导完成开关柜与干式变压器连接安装等一系列工作。 6.14 开关柜的其它要求

(1) 为方便地将开关柜上层抽屉放至地面,卖方应随开关柜提供可移动、可升降的搬运开关柜抽屉的小车。

(2) 开关柜柜内导体及其他部件的温升应符合国标 《低压成套开关设备》(GB7251)的规定。

(3) 开关柜的间隔应在每个回路上框架正面、电缆室接电缆处及抽屉或分隔面板上分别设置标志牌,标志牌采用有机玻璃、刻有设备名称和断路器的编号。

(4) 每段开关柜应设置贯穿整段配电装置全长的照明加热小母线。照明加热小母线为三相四线制,采用铜导体。连接在照明加热小母线上的负荷应尽可能的均匀布置,以保证照明加热小母线3相负荷的平衡。每一面开关柜均应设置照明装置,每一照明装置应设有的低压熔断器或小型断路器(须校核开关的短路容量),作为保护和操作设备,其电源由贯穿于整列柜的照明加热小母线供给。小型断路器的布置应不占

用开关柜的抽屉回路。

(5) 每面开关柜均应提供温湿度控制器及由交流220V电源供电的柜内空间电加热器,加热器应有自己的安全防护罩,加热器应安装在柜内既不会损坏又不会对人员构成危险的地方。加热器回路的短路保护设备、操作设备可采用小型断路器,显示设备可为信号灯,信号灯为红色,灯亮表示“加热器工作”。电加热器的运行与停止由温湿度控制器控制。电加热器的电源由贯穿于整列柜的照明加热小母线供给。加热器回路的设备和接线由卖方提供,电加热器回路的布置不应占用开关柜的抽屉,安装应在卖方的工厂完成。

(6) 辅助节点要求:提供足够用户使用的断路器或抽屉辅助接点,并引至开关柜端子排上。

(7) 降容系数:

- 低压开关柜及内部所有元器件在考虑当地海拔及其他气候因素,降容后

的技术参数不得低于本技术规格书所出现的参数要求。

- 外壳的防护等级为IP4X的开关柜,其每个抽出单元的电气元件的额定电

流的热降容系数不应低于95%(环境温度40℃)。

- 外壳的防护等级为IP4X的开关柜,其每个抽出单元的电气元件的额定电

流的热降容系数不应低于90%(环境温度40℃)。

(8) 导线标志和颜色规定如表6:

表6 导线标志和颜色规定

名 称 A相 B相 C相 中性线 地线 直流电源正极 直流电源负极 DC/AC控制回路 字 标 A B C N PE DC 220V (+) DC 220V (-) 按图纸中的线号 色 标 黄 绿 红 淡蓝色 黄绿相间 褐色 蓝色 按产品技术条件规定 (9)整套柜体在制造厂内联屏、试装配,确保现场不会因设备、部件尺寸误差等

因素造成安装问题。贯通主母线长度不小于3个柜,贯通母线工厂组装后,做好标记,分解发货,母线及外包装注明柜体方案编号和设备用途名称。

(10))贯穿主母线连接、小母线连接、联屏等安装紧固件属于开关柜设备的一部分,卖方应随设备主体一起发货。 6.15 铭牌和标志

(1) 每一台开关柜均应设一个铭牌,GB7251标准中第8.1条a~e项及m项的内容应在铭牌上给出,铭牌应装于每个柜正面的顶部。

(2) 开关柜的电气元件,应在尽可能靠近元件的上方标志文字符号,每电路的导线端头及每一个端子也应标志相应的文字符号。文字符号用耐檫的颜料打印,所有文字符号应与接线图上的文字符号一致。

(3) 每个回路应在开关柜正面和背面的对应位置有牢固、清晰的回路名称和编号标示,以满足运行、维护的需要。回路名称、编号将在详细设计阶段由设计院确定。

(4) 所有铭牌和标示的语言使用中英文。

7

7.1

试验

总则

设备应根据相关国标和行标等有关标准及其补充说明进行各项试验,有关条

款的特殊要求和补充应在试验期间遵守并执行。

所有试验的合格结果及其试验报告,并不能减轻或免除卖方对设备质量应当承担的全部责任。 7.2

型式试验

低压开关柜及其电气元件应进行标准的型式试验,试验项目和程序应按照有关国标和IEC的规范。型式试验应由国家认证的试验站进行,并应有合格的型式试验报告报买方审阅。

卖方应提供在相同低压开关柜及其电气元件上进行的各种型式试验证书,对于低于标准的试验,买方有权决定是否接受证书而取代制定的试验。

如果证书无效或不接受,卖方将负责以上型式试验的试验费用。 7.3

例行试验

所有低压开关柜及其电气元件均应在工厂内进行例行试验,例行试验根据有关国标和IEC的规范,并应有合格的例行试验合格证书供买方审阅。

7.4 现场试验

设备安装完好后,应进行现场交接试验。交接试验是为了确认设备在经过运

输、储存、现场安装和/或调整等过程后是否存在损坏、各个单元的兼容性、装配是否正确以及设备的正确特性。现场试验项目及试验要求原则上按照相关规范和产品技术条件规定的出厂试验项目进行,但若现场试验条件有限,买方可以不进行部分试验,卖方不得以此为借口免除或减轻自己对设备、部件和技术服务应负的责任。如现场试验结果不合格,经检查是设备自身质量和性能的原因,卖方应在买方规定的时间内通过修复、更换等方式予以纠正。

8

8.1

工厂检验与监造

概述

卖方按有关标准规程及合同的规定对设备在工厂进行制造、组装和试验。 买方将根据单方意愿选择是否参加工厂试验的目睹见证和产品的中间组装的

检查、见证。当买方有疑问要求进行验证设备性能的另外的试验时,卖方免费执行。在系统设计、制造过程中,买方对认为重要的技术方案进行专题审查。

卖方应对所供设备的质量、性能承担全部责任,买方对设备生产制造的检查和监督,以及对各项检验、试验的见证或认可,均不能构成减轻或免除卖方责任的理由。 8.2

试验要求

卖方在合同签订后4周内向买方提交5份工厂装配和试验项目清单,以及买方参加工厂装配和试验目睹见证安排计划。卖方在设备进行制造、组装、试验或检验前15天,向买方提供5份设备清单、试验或检验大纲,并说明技术要求、工艺、试验或检验方法、标准及时间安排,以便买方派人参加。

在工厂进行各项设备试验或检验后,向买方提供5套试验和检验报告复印件,报告包括试验方法、使用仪器的精度、计算公式、试验结果和照片等。报告经买方审查后,设备才能发运。

所有试验项目尽量模拟正常使用条件。对所有拆卸的部件,作出适当的配合标记和装设定位销,以保证在工地组装无误。对工厂组装、试验的设备,非安装需要,工地也可不进行解体,其装配质量和性能由卖方予以保证。 8.3

工厂制造、组装、试验目睹见证

买方将根据情况派代表参加工厂内制造、组装、试验的目睹见证。买方授权的代表在试验进行的任何时间和执行产品中间组装的监督、验收和检查期间,可以自由进出车间各地,卖方要给予方便而不收费,并免费提供所需的工具、量具及根据相应的标准提供满意的资料。

9

9.1

设计联络会

一般规定

为协调设备设计、工程设计及其它方面的工作,以保证合同有效及顺利地实

施,买方和卖方召开设计联络会。

合同双方在设计联络会上讨论设计方案、有关技术问题,协调与其它系统的工作与衔接、合同设备与其它系统设备的接口、资料交换、工作进度等。

设计联络会召开的时间与参加人员的数量,除按本合同规定外,由双方协商确定。由卖方编制每次会议的详细计划和日程,并按计划份数准备会议文件资料(包括图纸和电子文件等)和工作必需的设施,报买方同意后执行。

在设计联络会期间,买方有权就合同设备的技术方案、性能、参数、试验、工作与工程及其它系统设备的接口等方面的问题,进一步提出改进意见或对合同设备设计、试验和结构布置等补充技术条件和要求,卖方认真考虑并研究改进、予以满足。

设计联络会原则上召开一次,但之后若还有有重要问题需要双方开会研究和讨论,经协商增加设计联络会的次数,费用已包括合同价格中。在设计配合阶段,若双方同意,也可以不召开设计联络会。

设计联络会上买方对卖方的设计、设备的认可或批准,并不免除或减轻卖方根据合同应承担的责任与义务。 9.2

地点和内容

设计联络会计划在合同签定后30天左右举行,在设计联络会召开之前,卖方应完成了合同设备的初步设计,并至少提前1周向买方提供设备的外形图、基础图、单线图、部件参数、元器件清单和二次接线图。联络会将在买方所在地举行,讨论合同设备的设计方案和与其它设备卖方的设计协调,以及厂内设备的总体布置,审查结构、设计和质量保证体系,并讨论存在的技术问题,主要内容包括:

- 根据卖方提供的设计图纸资料,讨论设备的设计、参数、技术要求,与其它

系统的接口等;

- 讨论接线方式和连接要求;

- 讨论与其它设备供货厂家的协调配合问题; - 其它与设计有关的事项。 9.3

会议纪要

设计联络会将以会议纪要的形式确认双方协定的内容,卖方应接受设计联络会的意见、建议或要求,并在合同执行中遵守。在设计联络会期间如对合同条款、技术规范有重大修改时,或涉及合同额外费用时,须经过双方授权代表签字同意。设计联络会的会议纪要由卖方起草,经会议双方代表签字后生效。 9.4

其它

在设计联络会议期间,买方有权就设备问题进一步提出改进意见,卖方应认真考虑研究和改进。

设计联络会上确定的应提供的资料,卖方应在纪要规定的时间内提供给买方。 除联络会议外,由任一方提出的所有有关部件设计的更改,应经双方讨论并同意。一方接到任何需批复的文件或图纸后15天内,应将书面的批复或意见书返还提出问题方。

在合同有效期内,任一方应在15天内回答另一方提出的在技术文件范围内的任何设计和技术的问题。

10 现场技术指导和培训服务

10.1 概述

卖方应派遣至少1名工地总代表进行安装、调试的指导,并协调与买方以及与其他承包商之间的工作。

卖方应负责指导和监督合同设备的安装、试验、试运行,并参与合同设备的现场试验、验收等有关事项。

双方应根据工地的实际进展情况,协商决定卖方技术人员的准确专业、人员数量、在现场服务时间、以及到达和离开工地的日期。

卖方技术人员离开工地,须经买方同意。调试完毕应提供投运调试报告。 卖方应该编制1份详尽的安装调试时间表并提交给买方,指明安装调试所需时间,并列出所需的人员和工具的类型和数量。

10.2 任务和责任

卖方工地代表应常驻工地,并应在合同范围内全面负责技术服务和培训工作,与买方代表充分合作与协商,以解决与合同有关的问题,对买方工地代表提出的问题,应按期作出回答。

卖方技术人员应按合同规定进行有关合同设备的组装、安装、检查、调试、试运行、验收试验等的技术指导和培训并承担责任。

卖方技术人员应详细地解释技术文件、图纸、运行维护手册、设备特性、分析方法和有关的注意事项等以及解答和解决买方提出的技术问题。

为保证正确完成本项目的工作,卖方技术人员应在合同范围内,给买方以全面正确的技术服务和必要的示范操作。

卖方技术人员应在现场对合同设备组装、安装、试运行、验收试验、运行维护的相关人员进行培训,以提高他们的技术水平。

卖方技术人员的指导和培训应是正确的,如因卖方的错误或疏忽引起合同设备和材料的损坏,卖方应负责修复、更换和/或补充,其费用由卖方承担。 10.3 其它

卖方召回或调换工地技术人员必须征得买方同意,不得影响工地的工作。 买方视现场服务技术人员情况,有权要求卖方更换技术人员,卖方不得拒绝。 在质保期内,卖方将免费提供技术支持,当设备和部件出现质量问题需要卖方派技术人员到现场处理时,卖方也应及时免费提供相应的技术服务。质保期之后,卖方还应继续售后服务,帮助合同设备的完善和技术更新,以优惠的价格提供买方所需的元件、材料。

卖方应将技术服务费用,包括由工厂至现场的往返差旅费、服务人月数或人天数进行分项报价,买方只为卖方现场服务人员提供食宿。

11 质量保证

卖方所供全部设备和部件必须是全新的,持久耐用的,应满足作为一个完整产品所能满足的全部要求,卖方应对设备的质量、性能负全责。卖方应保证设备在规定的使用条件下运行、并按使用说明书进行安装和维护的预期寿命不少于30年。

订购的新型产品除应满足本技术规格书和相关标准外,卖方还应提供该产品的鉴定证书。

卖方应保证制造过程中的所有工艺、材料试验等(包括卖方的外购件在内)均应符合本技术规格书和相关标准的规定。若买方根据运行经验指定卖方提供某种外购零部件,卖方应积极配合。

附属及配套设备也必须满足有关标准的要求,并提供试验报告和产品合格证。 卖方应遵守本技术规范书和相关标准的规定,并满足ISO9000-GB/T19000质量保证体系的要求,该质量保证体系已经通过国家认证并在正常运转。

卖方所供的设备和部件质保期为自调试完成并投运后18个月,质保期内,卖方应免费修复或更换由于卖方的原因出现损坏或故障的设备和部件。之后如发生产品损坏,卖方应及时为本组装置提供维修部件,并按最近的投标价提供。

12 技术资料

12.1 一般要求

卖方提供的所有技术资料使用SI国际单位制,文字均用中英文对照,如有进口部件,其外文图纸及文件应由卖方免费翻译成中文。图纸应有标题栏、全部符号和部件标志。

卖方应根据买方提出的设计条件、技术要求、供货范围、保证条件等免费提供完整的技术资料,资料的组织结构清晰、逻辑性强。资料内容应正确、准确、一致、清晰、完整,满足工程要求。技术资料的交付进度应满足工程进度的要求。

对配合工程设计和随机的纸版文件应有相关有资格人员的完整、真实的认可签字。配合工程设计技术文件上应有“卖方公司公章”与“供工程设计”章。随机文件上应有“卖方公司公章”与“随机文件”章。修改版资料的修改内容应有明显的标识、修改人员的签名及修改日期。

没有列入的技术资料,如为工程所必需或买方要求的文件和资料,卖方也应及时免费提供。

各阶段卖方应提供的技术资料要求见表7。

表7 各阶段技术资料要求

阶段 配合设计资料 形式 纸版 电子版 数量 5套 2套 备注 3套给设计院,2套给买方。 包括OFFICE 2003、AUTOCAD 2004可编辑格式和PDF格式,1套给设计院,1套给买方。 随机资料 (中英文对照) 纸版 电子版 12套 3套 10套发往项目现场,2套发到买方国内工程部。 包括OFFICE 2003、AUTOCAD 2004可编辑格式和PDF格式,光盘储存,2套发往项目现场,1套发往买方国内工程部。 12.2 配合设计阶段的技术资料

所有需经买方确认的图纸和说明文件,均应由卖方在合同签订后的 1周内提交给买方进行审定认可。这些图纸资料包括设备外形图、安装图、开关柜配置图、控制接线图、土建基础设计资料等。

买方有权对供货设备的卖方图纸提出修改意见,凡买方认为需要修改且经卖方认可的,不得对买方增加费用。在未经买方对图纸作最后认可前,任何采购或加工的材料损失应由卖方单独承担。买方对资料图纸的认可或批准并不减轻或免除卖方所供设备的性能、质量、完整性及其图纸资料的正确性应当承担的全部责任。

卖方在收到买方的意见后,应于 2 周内向买方提供修改后的最终正式图纸资料。设备应按照经确认的最终图纸进行制造,完工后的产品应与最后确认的图纸一致。

设备在现场安装时,如卖方进一步修改图纸资料,卖方应对图纸资料重新收编成册,正式递交买方,并保证安装后的设备与图纸资料完全符合。 12.3 设备交货时的随机资料

卖方应在设备交货时提供满足安装、调试、试验、运行、维护要求的随机资料,随机资料应装订成册,随设备发运,包括但不限于如下图纸、说明书、试验报告和质量证书:

(1) 图纸和说明书

- 主接线图,包括设备及元器件配置、参数;

- 柜内接线图,包括端子排图等; - 设备外形尺寸图、布置图、装配图; - 主要设计数据、计算书;

- 开关柜、断路器、接触器、热继电器、软启动器、双电源转换开关等安装使用说明书、用户手册;

- 电流互感器、电压互感器使用说明书;

- 备自投装置、电动机保护器使用说明书、用户手册; - 测量仪表、变送器的使用说明书;

- 对于其他未列入但却是工程所必须的文件和资料及图纸。 (2) 试验报告和质量文件

- 设备及部件的制造记录、试验报告; - 设备及其部件的质量证书;

- 卖方或业主需要的其它试验报告和质量证书。

13 包装与运输

卖方应严格按照出口的要求对设备及部件进行包装,满足长时间海上、内陆运输以及现场露天储存的要求和规定。设备的包装应能保证设备各零部件在运输、储存过程中不致遭到脏污、损坏、变形、丢失及受潮。对于其中的绝缘部件及由有机绝缘材料制成的绝缘件应特别加以保护,以免损坏和受潮。对于外露的接触表面,应有预防腐蚀的措施。所有运输措施均应经过验证。如果由于包装的原因造成运输、储存期间设备损坏或丢失,卖方将负责免费修复或更换,若由此还引起的其它直接或间接的损失(如工期延误等),买方有权从合同余款中扣除等同的金额。

单独运输的零部件应有标志,便于用户安装装配。整体产品或分别运输的部件,都要适合于运输及装卸的要求。

备品备件、专用工具和仪器以及随机资料都应随同设备一起发运,每件包装箱都需附有详细的装箱单。所有技术资料、装箱单应有相应的保护措施,保证开箱时完整无缺。

其它详细的规定见附件11“设备及材料包装储运规定”。

14 附图

以下所有附图只是初步施工图设计的图纸,可能会根据实际设计的需要发生更改,卖方在采购、投产、加工前须就这些图纸获得买方的正式确认,若图纸有更改,卖方应以更改后的图纸为准。

附图1:380/220V 厂用电原理接线图 附图2:380/220V #1厂用动力中心接线图 附图3:380/220V #2厂用动力中心接线图 附图4:380/220V保安段配置接线图 附图5:380/220V备用配置接线图 附图6:综合主厂房汽机MCC接线图 附图7:综合主厂房主控楼MCC接线图 附图8:综合主厂房#1焚烧MCC接线图 附图9:综合泵房MCC接线图 附图10:油泵房MCC接线图

附图11:综合泵房消防巡检MCC接线图 附图12:主厂房消防MCC接线图 附图13:机修间配电柜接线图

附图14:低压配电室、10kV配电室布置平面图